Beer cooler not cooling: is the cabinet, the tower or the keg warm?

Warm beer and foamy beer are different problems. Take three temperatures to find whether the cabinet, the tower or the keg itself is the warm part.

(651) 395-3422
Quick answer

Is my beer warm because of the cabinet, the tower or the keg?

Take three readings: a liquid thermometer on a keg shelf, a probe in the first draw at the faucet, and the delivery history of the keg. A cabinet over 38°F is a refrigeration problem. A faucet reading far above the cabinet is a tower problem. A cold cabinet with a freshly delivered keg is a keg problem.

What three temperatures separate warm beer from foamy beer?

Warm beer and foamy beer get reported as one complaint, but the beer travels through three places on its way to the glass, and each can be the warm one. The cabinet holds the keg. The tower or shank carries the beer from the keg line to the faucet. The keg itself is a large mass of liquid that takes hours to change temperature in either direction. A single dial reading cannot tell you which of the three is wrong, so take one reading in each place and compare them.

For the cabinet, put a liquid thermometer in a glass of water or glycol on a keg shelf and leave it for a full day, so it reports what the beer sees and not what the dial says. The Brewers Association's Draught Beer Quality Manual puts air temperature in the cooler at 36 to 38°F and the liquid thermometer at 36 to 38°F, and says beer should be stored between 34 and 38°F. For the faucet, pull a small pour after the tap has been idle and put a probe into it right away. The same manual gives a serving range of 38 to 44°F, so a pour that lands well past the top of that range tells you the beer picked up heat after it left the keg.

Log the three readings with the time of the last keg delivery. The table at the end of this guide turns each pattern into a suspect. The foam question itself, meaning pressure, line length and dirty lines, belongs to the draught installer; the part this guide covers is whether the cooling side of the system is at fault. The repair side of the cooler is on the bar cooler repair page.

Is the keg itself still warm after delivery?

A keg is a poor place to look for a refrigeration fault, because kegs hold heat for a long time. The Brewers Association manual notes that a keg can warm from 38°F to 44°F in only four or five hours during delivery or storage at ambient temperature. It also gives a chill-down table: a keg that starts at 44°F needs about 18 hours in the cooler to get back to 38°F, and one that starts at 50°F needs about 25 hours. The manual adds that a keg that feels cold at 44°F may still need to chill overnight to dispense properly.

That timing explains a common pattern on the log. The cabinet liquid thermometer reads 37°F, the faucet draw reads warm, and a keg came off the truck that afternoon. Nothing is broken. The cabinet air is fine and the keg has not finished cooling. The test is to read the surface of the keg, or the first draw, again the next morning. If the draw has come down to the cabinet figure, the cause was keg handling.

If the same keg is still warm a full day after loading while the cabinet liquid thermometer is in range, the cooler cannot pull the load down, and the next section applies. If several kegs go in at once, expect a cabinet that was cold at noon to read warm after the load, because it has just absorbed a lot of heat. Staging kegs a day ahead, in a walk-in cooler where the bar has one, changes the problem from a service call into a schedule.

Is the cabinet failing to hold its temperature behind the bar?

A cabinet that stays above range on the liquid thermometer is a refrigeration problem, and bar placement causes many of them. Coolers sit in built-in cabinetry, in alcoves beside ice bins and under counters with cases stacked on top. A self-contained unit needs air through its condenser, and the data plate and installation manual say whether it breathes through a front or a rear grille. A grille behind a stack of liner boxes, or a back wall set too close, starves the condenser and the cabinet drifts up.

Bar air also loads the condenser fins with paper fibers, towel lint and kitchen grease. The Brewers Association manual notes that many draught system problems are revealed on the first hot day of the season because of missing preventive maintenance such as cleaning condenser fins on air-cooled systems, and its glycol-chiller checklist calls for a stiff bristle brush, a vacuum or compressed gas blown from the fan side. With the unit unplugged, a vacuum and brush on the coil, and a cleared grille, are the safe operator steps. Do not spray water on the coil.

Door traffic is the other load. A glass-door back-bar cooler exchanges cold air for warm humid air at every reach-in, and the moisture condenses on the evaporator. Frost cuts airflow until a defrost cycle clears it. A gasket that has hardened or a door that hangs a finger's width open means the unit never gets ahead. Thermostat settings drift too: a dial moved warmer to stop bottle sweat, or a control reprogrammed, can hold the box at 42°F while everyone assumes it is cold. Compare the liquid thermometer with the setting before concluding anything. A cooler that pulls down slowly, runs without stopping and still reads warm on a clean coil has a fan, a control or a sealed-system fault. See commercial refrigeration maintenance for the care that keeps coils clear, and the guide to a reach-in running warm for the checks that apply to any self-contained box.

Is the tower warming the beer between the keg and the glass?

When the cabinet and the keg are both in range and the faucet draw is warm, look at the tower. The manual explains that the line running through a tower to the faucet must be held at the cooler's temperature, that direct-draw towers are air cooled, and that they are insulated inside so cold air from the cooler circulates around the beer lines and shanks. Some boxes use corrugated tubing from the evaporator housing to carry cold air up into the tower, and the manual notes that this air comes straight from the evaporator discharge and is colder than the keg.

The reading to take is the gap between the cabinet liquid temperature and the faucet draw. A small gap is normal. A large gap points to the air path: a tube that has come loose from the evaporator housing, a tower fan that has stopped, insulation that has slumped, or a tower sitting under a hot light or in sun. Feel the base of the tower and the faucets. A tower that is cold at the base and warm at the faucets is losing cold on the way up.

Reseating a loose air tube is something an operator can do with the unit off. A dead tower fan, or an evaporator that no longer feeds the tower, is a technician repair. A Perlick or True direct-draw box follows the same principle. The bar cooler repair page covers the foam symptoms that follow from a warm tower.

What if every temperature is in range and the beer still foams?

Then the cooling side is probably innocent. The manual's direct-draw troubleshooting lists beer that is too warm as a cause of foaming, and it also lists beer that is too cold or frozen in the lines as a cause, so a dial turned colder to chase foam can make the pour worse. Its checklist gives gas pressure for a direct-draw system on 100 percent CO2 for ales and lagers as 12 to 15 psi, and lists lines full of beer and free of bubbles or kinks.

Regulators, blenders, glycol power packs and long-draw lines are a draught installer's work, as is the beer distributor's line cleaning. A cooler visit should end with the three readings in hand, so that the installer starts from a known cabinet, keg and tower temperature instead of guessing. Bars with heavy tap lists and ice traffic are covered under bars and breweries.

ReadingWhat it points toWho fixes it
Cabinet liquid thermometer above 38°F, bottles cool not coldDirty condenser, blocked grille, door leak, drifted setting or a weak systemStaff clear the coil and grille; technician if it persists
Cabinet in range, faucet draw warm, tower warm to the touchAir path to the tower broken, tower fan stopped or insulation slumpedStaff reseat a loose tube; technician for the fan
Cabinet in range, keg delivered within the dayKeg has not finished chillingStaff, by staging kegs ahead
Cabinet drifts up after each delivery and recovers overnightLoad pulls the box down slowly; marginal coil, fan or door sealTechnician if recovery takes longer each week
Beer slushy or freezing in the linesSetting too cold or a failed controlTechnician; staff record the dial
Every reading in range, still foamGas pressure, line length or dirty linesDraught installer or beer supplier
Compressor runs, cabinet never coolsLow charge or a sealed-system faultTechnician (EPA Section 608 certification required for refrigerant work)

A safe sequence to follow

  1. Put a liquid thermometer on a keg shelf

    Set it in a glass of water or glycol and read it after a full day, not right after a delivery.

  2. Probe the first draw

    Pour a small amount at the faucet after a quiet spell and put a probe in it at once.

  3. Note the last keg delivery

    Write the time against the readings, since a keg takes many hours to chill.

  4. Compare the three numbers

    Cabinet, faucet and keg history show which part is warm; do not turn the dial colder to chase foam.

  5. Clear the grilles and the condenser

    With the plug pulled, remove cases and towels from the vent, then vacuum and brush the fins without spraying water.

  6. Feel the tower

    Compare the base of the tower to the faucets, and confirm the cooling tube or fan, where there is one, is seated.

When to stop and call

  • The liquid thermometer stays above 38°F after the coil, grille and door are clear.
  • The evaporator or condenser fan is not turning, or the compressor hums and does not start.
  • Ice builds on the coil or water leaks inside the cabinet.
  • The tower never gets cold even though the box does.
  • Beer freezes in the lines, or the cabinet swings by several degrees between readings.

Questions about this problem

How long does a keg take to cool after it is delivered warm?

The Brewers Association manual lists about 18 hours in the cooler for a keg that starts at 44°F to reach 38°F, and about 25 hours from 50°F. A keg that has warmed only to 44°F can still need to chill overnight, so a cold cabinet does not mean a cold keg.

Can the cooler dial tell me what temperature the beer is?

No. A dial or display reads an air or coil temperature near the evaporator. A liquid thermometer in the cabinet reads closer to what the keg sees, and a probe in a poured sample reads what the guest gets. Use the liquid thermometer for the cabinet and the probe for the glass.

Why does my back-bar cooler read cold in the morning and warm by the weekend rush?

Door openings and fresh stock add heat faster than a marginal system removes it. A dirty condenser, a stalled evaporator fan or a worn gasket leaves little reserve, so the box holds when the bar is quiet and drifts when it is busy. Clear the grille and coil first, then log the temperature through a shift.

Should I turn the thermostat colder if the beer is warm?

Only after the liquid thermometer shows the cabinet really is warm and the coil and grille are clear. A lower setting will not help a stopped fan or a blocked condenser. The manual also lists beer that is too cold or frozen in the lines as a cause of foam, so colder is not a safe default.

Who services glycol-cooled long-draw lines and CO2 regulators?

A draught installer or the beer distributor's line technician. Long-draw glycol systems, gas regulators and blenders are a different trade from the cabinet's compressor, condenser, fans and controls. If the cabinet, keg and tower readings are all in range and foam persists, hand the three readings to that installer.

Sources